Power station runtime, explained honestly
Every runtime claim in every power station ad comes from one formula. Once you know it — and the one adjustment honest calculations make — you can size a station for your own appliances better than any "best for" list can.
Watts are speed, watt-hours are the fuel tank
- Watts (W) measure power right now — how hard something is drawing at this instant. A station's output rating (e.g. 2,400W) is the most it can supply at once.
- Watt-hours (Wh) measure stored energy — watts × hours. A 2,048Wh station holds enough energy to deliver 2,048 watts for one hour, 1,024 watts for two hours, 100 watts for about twenty hours, and so on.
- Kilowatt-hours (kWh) are just 1,000Wh — the unit on your electric bill and your fridge's EnergyGuide label.
The formula: runtime (hours) ≈ usable Wh ÷ average watts
The honest adjustment: usable Wh ≈ rated Wh × 0.85. The inverter that converts battery power to household AC loses roughly 10–15%, and no plan should end at absolute zero. If a runtime claim doesn't mention losses, it used the full nameplate number — discount it.
The catch: most appliances don't draw their label watts
The formula needs average watts, and that's where people go wrong. Three patterns cover most of the house:
- Cycling loads (fridge, freezer): draw real watts only part of the time. Don't use running watts — use the appliance's daily energy (EnergyGuide kWh/year ÷ 365). A fridge "drawing 150W" typically averages 45–85W over a day.
- Steady loads (CPAP, router, lights, TV): draw roughly their rated watts the whole time they're on. These are easy: watts × hours = Wh.
- Motor loads (sump pump, well pump): modest running watts but a starting surge of 2–3× that your station's surge rating must clear, plus a runtime that depends on how often they fire.
Typical appliance draws (for planning)
| Appliance | Draw while on | Planning figure |
|---|---|---|
| Full-size fridge | 100–250 W, cycling | ~1.1 kWh/day (standard) — use your EnergyGuide |
| CPAP | 11–59 W depending on humidifier | 89–472 Wh per night (ResMed AirSense 10 data) |
| Sump pump ⅓ HP / ½ HP | ~800 W / ~1,050 W + surge | Watts × minutes-per-hour ÷ 60 |
| Wi-Fi router + modem | ~10 W | ~240 Wh/day if left on |
| LED light bulb | ~10 W each | 4 bulbs × 5 evening hours ≈ 200 Wh |
| TV (modern LED) | ~80–150 W | ~120 W × hours watched |
| Phone charging | ~10–20 W | ~15–25 Wh per full charge |
| Laptop | ~30–65 W in use | ~50 W × work hours |
| Microwave | ~1,000–1,200 W | 15 min of use ≈ 250–300 Wh |
| Coffee maker | ~800–1,200 W while brewing | One brew cycle ≈ 60–100 Wh |
| Space heater | ~1,500 W | ~1,500 Wh per hour — see the warning below |
Fridge, CPAP, and pump figures are from the manufacturer/EnergyGuide sources cited on their dedicated pages. The rest are typical published ranges for common models, checked November 2026 — fine for planning, and your own appliances' labels beat any table.
The worksheet: size a station for your outage
Step 1 — list what must run, and for how long, in a 24-hour outage day. (Fridge: 24h. CPAP: 8h. Lights: 5h. Router: 24h or only waking hours — your call.)
Step 2 — convert each to Wh per day using the patterns above: steady loads watts × hours; cycling loads from daily energy figures; motors from minutes-per-hour.
Step 3 — add it up, then divide by 0.85. That's the rated capacity you need per day of outage.
Step 4 — check the watts, not just the watt-hours: add up everything that could run at the same moment, and confirm the station's continuous output covers it — and its surge rating covers the biggest motor's start.
Step 5 — decide your days. Multiply by the outage length you want to cover, or plan on solar recharging to cover the daily total (a panel array roughly equal to your daily Wh in rated watts, in decent sun, is the usual starting estimate — see the cost guide).
A worked example: a realistic essentials list
| Load | Math | Wh per day |
|---|---|---|
| Standard fridge | EnergyGuide ~1.1 kWh/day | 1,100 |
| CPAP, humidifier on low | ~28 W × 8 h | ~221 |
| Wi-Fi router | 10 W × 16 h (off overnight) | 160 |
| 4 LED lights | 40 W × 5 h | 200 |
| 2 phones + laptop top-up | flat estimate | ~100 |
| Total | ~1,781 Wh/day |
1,781 ÷ 0.85 ≈ 2,095Wh of rated capacity per outage day — which is why the ~2kWh class is the home-backup sweet spot: it covers a realistic essentials list for a day, and a fridge-plus-CPAP-only list for considerably longer. A ~1kWh station covers the same list for about half a day, or a trimmed list (fridge + lights, CPAP moved to its own small station) overnight. Neither is "wrong" — it depends which day of the outage you're planning for.
Three mistakes that make stations disappoint
- Sizing from nameplate watts. "My fridge is 150W and the station is 1,000Wh, so 6.6 hours" — wrong in both directions (the fridge cycles; the station has losses). Use daily energy.
- Forgetting surge. A station can have plenty of Wh and still refuse to start a sump pump or an older fridge compressor. Surge rating is a separate spec — check it.
- Planning around heat. Space heaters, hair dryers, kettles, and electric blankets are battery-eaters: a 1,500W heater empties a 2kWh station in about an hour. In a winter outage, a station keeps the fridge, the CPAP, and the lights going — warmth has to come from insulation, layers, and a safe non-electric heat plan, not from a battery this size.
Ready to apply it? The dedicated guides run the same worksheet for a fridge, a CPAP, and a sump pump — or skip to the 2kWh stations compared if your math already landed you there.